Natural Gas Detector & HPD Gas Leak Notice Requirements for 2027 (pdf,NYC Local Law 157)

(No reviews yet) Write a Review
SKU:
Natural Gas Detector & HPD Gas Leak Notice Requirements for 2027 (pdf,NYC Local Law 157)
MPN:
All-Electric Building Sign NYC | HPD Ins
  • Natural Gas Detector & HPD Gas Leak Notice Requirements for 2027 (pdf,NYC Local Law 157)
  • Natural Gas Detector & HPD Gas Leak Notice Requirements for 2027 (pdf,NYC Local Law 157)
  • Natural Gas Detector & HPD Gas Leak Notice Requirements for 2027 (pdf,NYC Local Law 157)
  • Natural Gas Detector & HPD Gas Leak Notice Requirements for 2027 (pdf,NYC Local Law 157)
  • Natural Gas Detector & HPD Gas Leak Notice Requirements for 2027 (pdf,NYC Local Law 157)
  • Natural Gas Detector & HPD Gas Leak Notice Requirements for 2027 (pdf,NYC Local Law 157)
  • Natural Gas Detector & HPD Gas Leak Notice Requirements for 2027 (pdf,NYC Local Law 157)
$0.00
Frequently bought together:

Description

NYC Local Law 157: Natural Gas Detector Requirements for 2027 – Complete Guide for Property Owners

NYC Natural Gas Detector Law: What Building Owners Need to Know

New York City Local Law 157 of 2016 requires natural gas detecting devices in residential buildings with gas piping or gas service. The law is designed to protect residents by providing early warnings of natural gas leaks, helping prevent fires, explosions, and other potentially dangerous situations.

The requirements apply to covered residential properties throughout Brooklyn, Manhattan, Queens, the Bronx, and Staten Island.

The NYC Department of Buildings (DOB) adopted regulations incorporating NFPA 715-2023, the national standard for fuel gas detection and warning equipment.

The current compliance deadline is January 1, 2027, subject to a possible extension to January 1, 2029.

Property owners should understand three important requirements:

  1. Install approved natural gas detectors in required locations.

  2. Post the required Natural Gas Detector Notice in the building entrance area, where applicable.

  3. Post the separate HPD Gas Leak Notice explaining emergency procedures.

1. What Is NYC Local Law 157?

Local Law 157 was enacted in 2016 to improve natural gas safety in New York City residential buildings.

The law amended the NYC Housing Maintenance Code and Building Code to require natural gas detection equipment in covered residential properties.

The NYC Department of Buildings adopted implementing regulations on February 12, 2024, including:

  • 1 RCNY §908-02 — Standards for Installation and Location of Natural Gas Alarms.

  • 1 RCNY §3616-06 — Amendments relating to NFPA 715.

  • NFPA 715-2023 — Standard for the Installation of Fuel Gases Detection and Warning Equipment.

The original installation deadline was May 1, 2025. Local Law 102 of 2025 subsequently changed the deadline to January 1, 2027, with a provision allowing an extension to January 1, 2029 under specified conditions.

2. Which NYC Buildings Must Install Natural Gas Detectors?

Natural gas detector requirements generally apply to the following residential properties:

Private Dwellings

One-family and two-family homes with gas piping or gas service must comply with applicable natural gas alarm requirements.

Class A Multiple Dwellings

Residential apartment buildings, including rental apartments and other covered Class A dwellings, must have natural gas detection protection in accordance with the regulations.

Class B Multiple Dwellings

Certain transient residential buildings may comply through natural gas alarms installed in individual dwelling units or through a qualifying professionally designed zoned detection system.

Buildings Without Gas Service

Buildings without gas piping or gas service are exempt from the natural gas detector installation requirements under 1 RCNY §908-02.

Important: An apartment without a gas stove is not automatically exempt when the building itself has gas piping or gas service.

3. Where Must Natural Gas Detectors Be Installed?

Natural gas detectors must be installed in accordance with NYC DOB regulations and the manufacturer's instructions.

When a gas-burning appliance is located inside a dwelling, the detector must generally be installed in the same room as the appliance.

NYC Natural Gas Detector Placement Requirements:

  • Install the detector at least 3 feet from the gas-burning appliance.

  • Install the detector no more than 10 feet from the appliance.

  • Measure the distance horizontally.

  • Install the detector on the ceiling or on a wall.

  • For wall installation, position the detector no more than 12 inches below the ceiling.

  • Follow the manufacturer's installation instructions and applicable NFPA 715 requirements.

Exceptions may apply when the room does not allow installation at least 3 feet from the appliance or when the manufacturer or NFPA 715 specifies a different location.

4. Where to Install Natural Gas Detectors in a Home or Apartment

The following locations should be evaluated whenever they contain gas-burning appliances.

Kitchen

Gas appliances may include:

  • Gas stove

  • Gas oven

  • Gas cooktop

Install an approved natural gas detector in the same room, following the required horizontal distance and mounting height.

Living Room

Gas appliances may include:

  • Gas fireplace

  • Gas space heater

Install a detector where required, following the manufacturer's instructions and applicable NYC placement rules.

Bathroom or Adjacent Utility Closet

Gas appliances may include:

  • Gas wall heater

  • Gas tankless water heater

Detector placement depends on the appliance location, room conditions, and applicable installation requirements.

Laundry Room

Gas appliances may include:

  • Gas clothes dryer

Install a detector in the same room when required.

Basement or Mechanical Room

Gas appliances may include:

  • Gas furnace

  • Gas boiler

  • Gas hot water heater

  • Gas tankless water heater

  • Gas-fired heating equipment

These locations should be evaluated under applicable building, mechanical, and fire-safety requirements. Requirements for common mechanical rooms may differ from those for appliances inside dwelling units.

Garage

Gas appliances may include:

  • Gas water heater

  • Gas space heater

  • Gas-powered equipment

Detector placement must follow applicable code provisions and the manufacturer's instructions.

Dining Room

Where a gas fireplace or other gas-burning appliance is installed, evaluate the location for required natural gas detection.

5. What Type of Natural Gas Detector Is Required in NYC?

Natural gas detectors must meet applicable NYC DOB requirements.

Under 1 RCNY §908-02, natural gas alarms must:

  • Comply with applicable NFPA 715-2023 requirements.

  • Be listed and labeled under UL 1484 or UL 2075, as applicable.

  • Identify the manufacturer.

  • Be installed in an approved location.

  • Be maintained in good working condition.

A standard smoke detector or carbon monoxide detector does not automatically detect natural gas.

Only devices specifically approved for natural gas detection should be used to satisfy the applicable requirement.

6. Battery-Powered, Plug-In, and Hardwired Natural Gas Detectors

NYC regulations distinguish between different detector installation methods.

Battery-Powered Natural Gas Detectors

Qualifying battery-powered alarms may be installed by property owners, maintenance personnel, occupants, or other individuals without requiring a licensed electrical contractor solely for that installation.

However, battery-powered equipment must satisfy applicable code and power-source requirements.

Plug-In Natural Gas Detectors

Qualifying plug-in alarms may also be installed without a licensed electrical contractor, provided the installation complies with applicable regulations and manufacturer instructions.

Hardwired Natural Gas Detectors

Hardwired installations generally require an NYC-licensed electrical contractor and applicable permits.

Property owners should verify that the selected device and power source are acceptable for their building before installation.

7. NYC Natural Gas Detector Notice Sign Requirements

In addition to installing natural gas detectors, covered NYC residential building owners must comply with HPD notice requirements.

The Natural Gas Detector Notice informs occupants about the installation, maintenance, repair, replacement, and responsibilities associated with natural gas alarms.

Where to Install the Natural Gas Detector Notice Sign

For covered Class A multiple dwellings, the notice must be posted in the required building entrance area.

A visible location in the lobby or entrance area is generally appropriate, provided the posting meets applicable HPD requirements.

The notice should be easy for residents to see and read.

Property owners must also provide required information to occupants regarding detector testing, maintenance, and responsibilities.

Approved combined detector notices may be permitted under HPD regulations.

8. NYC HPD Gas Leak Notice Sign Requirements

The Gas Leak Notice is a separate requirement from the Natural Gas Detector Notice.

The HPD Gas Leak Notice explains the procedures residents must follow if they suspect a natural gas leak.

The notice is commonly titled:

PROCEDURE FOR TENANTS REGARDING SUSPECTED GAS LEAKS

The notice includes emergency instructions in English and Spanish and identifies the building's gas service provider.

Where to Install the Gas Leak Notice

For covered residential buildings, the notice must be posted in a readily visible common area.

A building lobby or entrance area is generally an appropriate location.

Property owners must also provide the required notice to tenants and prospective tenants in accordance with HPD regulations.

What to Do if You Smell Gas

Residents should follow these emergency procedures:

  1. Quickly open nearby doors and windows if safe, and leave the building immediately.

  2. Do not attempt to locate the leak.

  3. Do not turn electrical appliances or switches on or off.

  4. Do not smoke or use matches or lighters.

  5. Do not use a telephone inside the building.

  6. Once outside and safely away from the building, call 911.

  7. Contact the building's gas service provider from a safe location.

Never attempt to repair a suspected natural gas leak yourself.

9. Natural Gas Detector Notice vs. Gas Leak Notice

Although both notices concern natural gas safety, they serve different purposes.

Natural Gas Detector Notice

  • Explains natural gas detector requirements.

  • Addresses installation and replacement.

  • Describes owner and occupant responsibilities.

  • Provides information about maintenance and applicable charges.

Gas Leak Notice

  • Explains emergency procedures when gas is suspected.

  • Instructs residents to evacuate.

  • Explains when to contact 911.

  • Provides gas service provider information.

Important: Installing a natural gas detector does not eliminate the separate Gas Leak Notice requirement.

Similarly, posting a Gas Leak Notice does not replace the obligation to install required natural gas detectors.

10. Who Is Responsible for Natural Gas Detector Installation?

Property Owner Responsibilities

Owners of covered residential buildings are generally responsible for:

  • Providing required natural gas detectors.

  • Ensuring initial installation complies with NYC regulations.

  • Posting required building notices.

  • Providing required tenant information.

  • Replacing detectors when required.

  • Maintaining applicable compliance records.

Tenant Responsibilities

Tenants generally have responsibilities relating to:

  • Routine detector testing.

  • Keeping detectors unobstructed.

  • Replacing ordinary batteries where applicable.

  • Reporting missing, damaged, or malfunctioning detectors.

  • Not removing, disabling, or tampering with installed detectors.

The allocation of maintenance and replacement responsibilities depends on the applicable HPD regulations and circumstances.

11. Can NYC Landlords Charge Tenants for Natural Gas Detectors?

HPD regulations permit certain limited charges for qualifying detector installations and replacements.

The applicable notice identifies the following maximum charges:

  • $25 for a natural gas detector.

  • $50 for a natural gas detector combined with a smoke detector or carbon monoxide detector.

  • $75 for a combined smoke, carbon monoxide, and natural gas detector.

These are not unrestricted maintenance fees.

Charges must comply with applicable HPD rules, including restrictions and exceptions concerning when an occupant may be charged.

12. When Must Natural Gas Detectors Be Replaced?

Natural gas detectors have a manufacturer-specified useful life.

Property owners and occupants should review the manufacturer's instructions to determine when replacement is required.

A detector may also require replacement if it:

  • Reaches the end of its useful life.

  • Becomes inoperable.

  • Is damaged.

  • Is missing or removed.

  • Cannot be restored to proper working condition.

Property owners should keep records of installation dates and anticipated replacement dates.

13. NYC Local Law 157 Compliance Checklist for Building Owners

Before the applicable compliance deadline, property owners should complete the following:

  1. Determine whether the building has natural gas piping or service.

  2. Identify all covered residential dwelling units.

  3. Identify gas-burning appliances and required detector locations.

  4. Select properly listed and compliant natural gas detectors.

  5. Confirm acceptable battery, plug-in, or hardwired power arrangements.

  6. Install detectors according to NYC DOB requirements.

  7. Provide occupants with required testing and maintenance instructions.

  8. Post the Natural Gas Detector Notice in the required entrance area.

  9. Post the separate HPD Gas Leak Notice in a visible common area.

  10. Verify that the gas service provider information is accurate.

  11. Maintain records of detector installation and replacement.

  12. Monitor NYC DOB and HPD announcements concerning the final compliance deadline.

14. Frequently Asked Questions About NYC Local Law 157

Does Every NYC Apartment Need a Natural Gas Detector?

Covered residential buildings with gas piping or gas service generally must provide natural gas detection protection. Specific installation requirements depend on building classification, appliances, and applicable exceptions.

Does a Natural Gas Detector Have to Be Installed Near the Stove?

When a gas stove is installed inside a dwelling, a detector must generally be installed in the same room, between 3 and 10 feet horizontally from the appliance, unless an applicable exception requires a different location.

Can a Natural Gas Detector Be Installed on the Wall?

Yes. The general NYC DOB rule permits wall installation no more than 12 inches below the ceiling.

Does a Building Without Gas Service Need Natural Gas Detectors?

Buildings without gas piping or gas service are exempt under the applicable DOB rule.

Is a Natural Gas Detector Required in the Building Lobby?

A lobby notice and a detector are separate requirements. A standalone lobby detector is not automatically required merely because the building must post a notice. Certain Class B multiple dwellings may use qualifying zoned detection systems in common areas.

Is a Carbon Monoxide Detector the Same as a Natural Gas Detector?

No. Carbon monoxide detectors identify carbon monoxide, while natural gas detectors identify combustible natural gas. Some combination devices provide multiple detection functions when appropriately listed and approved.

Can a Landlord Install Natural Gas Detectors Without an Electrician?

Qualifying battery-powered and plug-in natural gas detectors may be installed without a licensed electrical contractor. Hardwired installations generally require licensed electrical work.

Are Natural Gas Detector Signs and Gas Leak Signs the Same?

No. The Natural Gas Detector Notice explains detector requirements and responsibilities. The Gas Leak Notice provides emergency instructions for suspected gas leaks.

What Is the NYC Natural Gas Detector Deadline?

The currently published compliance deadline is January 1, 2027, subject to a possible extension to January 1, 2029 under Local Law 102 of 2025.

Property owners should verify the latest official NYC DOB and HPD announcements before relying on the deadline.

15. Official NYC Natural Gas Detector Regulations and Resources

For additional information, consult:

NYC Department of Buildings

1 RCNY §908-02 — Standards for Installation and Location of Natural Gas Alarms.

1 RCNY §3616-06 — NFPA 715 Amendments.

Website: https://www.nyc.gov/site/buildings/index.page

NYC Department of Housing Preservation and Development

Natural Gas Detector Requirements:

https://www.nyc.gov/site/hpd/services-and-information/detectors.page

Required Signs and Notices:

https://www.nyc.gov/site/hpd/services-and-information/required-signage.page

NFPA 715-2023

Standard for the Installation of Fuel Gases Detection and Warning Equipment.

Conclusion: NYC Natural Gas Detector Requirements for 2027

NYC Local Law 157 establishes important natural gas detection requirements intended to improve safety in residential buildings.

Owners of covered properties should ensure that approved detectors are installed in required locations and that all applicable HPD notices are properly posted.

For many residential buildings, compliance involves three separate safety measures:

1. Natural Gas Detector Notice Sign — Post in the required building entrance area.

2. HPD Gas Leak Notice — Post in a visible common area and provide required tenant notices.

3. Natural Gas Detectors — Install in required locations within residential dwelling units, including rooms containing gas-burning appliances.

Property owners should verify the applicable deadline, approved detector specifications, and installation requirements before completing their compliance work.


Provided by: HPDSigns.NYC

NYC HPD Signs, Gas Leak Notices, Natural Gas Detector Notices, and Building Safety Signage.

Website: https://hpdsigns.nyc

Disclaimer: This article is provided for general educational purposes and reflects NYC requirements and published guidance available as of November 2026. HPDSigns.NYC is an independent signage supplier and is not affiliated with NYC HPD, DOB, or any government agency. Property owners are responsible for verifying current legal requirements, applicable exemptions, installation conditions, and compliance deadlines. HPDSigns.NYC supplies signs and does not install natural gas detectors.

 

 

Disclaimer

This information is provided for general educational and informational purposes only and should not be considered legal, engineering, architectural, code compliance, or professional advice. Building regulations, zoning requirements, Certificates of Occupancy, and applicable New York City laws may vary depending on the property's occupancy classification, construction type, alteration history, and location. Always consult the current New York City Building Code, Housing Maintenance Code, Fire Code, Zoning Resolution, the appropriate city agencies, and/or a licensed architect, professional engineer, or qualified code consultant before making decisions regarding the alteration, rental, occupancy, or use of any basement or cellar space.

 
 

LEGAL DISCLAIMER, LIMITATION OF LIABILITY, AND TERMS OF USE

INDEPENDENT SMALL FAMILY-OWNED BUSINESS NOTICE

We are an independent privately owned small family-owned business operating in the United States.

We are NOT the City of New York, HPD, DOB, FDNY, DSNY, DEP, DOT, DHCR, HUD, OSHA, EPA, FEMA, any state agency, any federal agency, or any governmental, quasi-governmental, regulatory, enforcement, housing, building, fire, transportation, sanitation, environmental, health, public safety, or public authority organization.

We are not affiliated with, endorsed by, approved by, sponsored by, authorized by, certified by, partnered with, or connected in any manner with any governmental agency or authority.

Any references to governmental agencies, laws, regulations, codes, standards, ordinances, inspections, notices, permits, requirements, compliance programs, enforcement actions, or public resources are provided solely for informational and descriptive purposes and do not imply endorsement, approval, certification, sponsorship, authorization, partnership, or affiliation.

Many governmental publications, flyers, brochures, forms, notices, checklists, and educational materials referenced, reproduced, summarized, attached, linked, or distributed by our company are publicly available documents that may be obtained directly from the applicable government agency, often at no charge.

INFORMATIONAL PURPOSES ONLY

All content, products, services, signs, sign packages, notices, brochures, flyers, downloadable files, PDF documents, checklists, product descriptions, blog articles, compliance guides, customer communications, emails, specifications, marketing materials, and related information are provided solely for general informational and educational purposes.

Information may become outdated, amended, revised, superseded, interpreted differently, or withdrawn without notice.

Laws, regulations, building codes, fire codes, housing requirements, inspection procedures, accessibility requirements, environmental regulations, insurance requirements, safety standards, and governmental policies frequently change and may vary by jurisdiction, occupancy type, building classification, property use, location, agency interpretation, and individual circumstances.

We make no representation, warranty, or guarantee that any information provided is accurate, complete, current, reliable, applicable, legally sufficient, or appropriate for any specific situation.

Users assume all risk associated with reliance upon any information provided.

NO PROFESSIONAL ADVICE

Nothing provided by our company shall be construed as:

• Legal advice
• Engineering advice
• Architectural advice
• Fire protection advice
• Life safety advice
• Accessibility advice
• ADA compliance advice
• Building code advice
• Fire code advice
• Housing code advice
• Inspection advice
• Regulatory advice
• Tax advice
• Insurance advice
• Real estate advice
• Environmental advice
• Construction advice
• Property management advice
• Professional consulting services of any kind

No attorney-client, consultant-client, architect-client, engineer-client, contractor-client, professional-client, or fiduciary relationship is created through the use of our website, purchase of products, receipt of materials, or communication with our company.

Customers should consult qualified attorneys, architects, engineers, code consultants, licensed contractors, fire protection professionals, insurance professionals, accountants, and applicable governmental authorities regarding their specific circumstances.

GOVERNMENT PUBLICATION DISCLAIMER

Any government-related document, brochure, flyer, checklist, guide, notice, publication, form, or educational material distributed by our company is provided solely as a convenience to customers.

Such materials remain the property of their respective agencies and organizations.

Our company does not create, maintain, update, approve, certify, validate, or control the contents of such governmental publications.

Government agencies may revise, amend, replace, withdraw, reinterpret, or update such materials at any time without notice.

Customers should always consult the original official governmental source for the most current information.

Official government publications, agency guidance, statutes, regulations, rules, code provisions, interpretations, and enforcement positions shall always control over any summary, reproduction, attachment, description, reference, or explanation provided by our company.

CUSTOMER RESPONSIBILITY FOR COMPLIANCE

The customer, property owner, landlord, management company, architect, engineer, contractor, installer, purchaser, building owner, consultant, and end user bear sole and exclusive responsibility for determining:

• Whether signage is required
• What signage is required
• Applicable laws and regulations
• Sign wording and content
• Sign dimensions and specifications
• Material requirements
• Installation requirements
• Placement requirements
• Inspection requirements
• Permit requirements
• Accessibility requirements
• Fire safety requirements
• Building safety requirements
• Environmental requirements
• Insurance requirements
• Operational requirements

Purchasing any sign, sign package, decal, placard, marker, notice, template, guide, checklist, flyer, brochure, or informational material from us does not constitute compliance with any law, code, regulation, ordinance, permit, inspection requirement, insurance requirement, governmental directive, court order, or regulatory obligation.

SIGNAGE DISCLAIMER

All signs, labels, notices, placards, decals, markers, plates, directories, room identification signs, building signs, compliance signs, and related products are provided solely as physical products.

We do not certify, guarantee, warrant, represent, or promise that any product:

• Meets any legal requirement
• Meets any code requirement
• Passes any inspection
• Satisfies any governmental requirement
• Creates legal compliance
• Creates regulatory compliance
• Meets insurance requirements
• Meets accessibility requirements
• Meets ADA requirements
• Meets OSHA requirements
• Meets FDNY requirements
• Meets HPD requirements
• Meets DOB requirements
• Prevents injury or property damage
• Eliminates legal obligations
• Eliminates regulatory obligations

The purchaser is solely responsible for determining suitability for the intended application.

INSTALLATION DISCLAIMER

Improper installation may create safety hazards, accessibility issues, regulatory violations, inspection failures, property damage, personal injury, or death.

We assume no responsibility whatsoever for:

• Installation methods
• Installation locations
• Placement decisions
• Fasteners selected
• Adhesive selection
• Structural attachment methods
• Mounting surfaces
• Electrical connections
• Maintenance practices
• Visibility requirements
• Accessibility requirements
• Inspection outcomes

All installation decisions remain the sole responsibility of the purchaser, installer, contractor, property owner, and building owner.

DISCLAIMER OF WARRANTIES

TO THE MAXIMUM EXTENT PERMITTED BY LAW, ALL PRODUCTS, SERVICES, INFORMATION, DOCUMENTS, DOWNLOADS, PUBLICATIONS, COMMUNICATIONS, AND MATERIALS ARE PROVIDED "AS IS," "WITH ALL FAULTS," AND "AS AVAILABLE."

WE EXPRESSLY DISCLAIM ALL WARRANTIES OF ANY KIND, WHETHER EXPRESS, IMPLIED, STATUTORY, OR OTHERWISE, INCLUDING WITHOUT LIMITATION:

• MERCHANTABILITY
• FITNESS FOR A PARTICULAR PURPOSE
• NON-INFRINGEMENT
• ACCURACY
• COMPLETENESS
• RELIABILITY
• PERFORMANCE
• DURABILITY
• CODE COMPLIANCE
• REGULATORY COMPLIANCE
• INSPECTION APPROVAL

NO ORAL OR WRITTEN STATEMENT SHALL CREATE ANY WARRANTY NOT EXPRESSLY SET FORTH IN A WRITTEN AGREEMENT SIGNED BY AN AUTHORIZED REPRESENTATIVE OF OUR COMPANY.

LIMITATION OF LIABILITY

TO THE MAXIMUM EXTENT PERMITTED BY LAW, OUR COMPANY, ITS OWNERS, FAMILY MEMBERS, EMPLOYEES, OFFICERS, DIRECTORS, AGENTS, REPRESENTATIVES, CONTRACTORS, SUCCESSORS, ASSIGNS, SUPPLIERS, DISTRIBUTORS, AFFILIATES, AND SERVICE PROVIDERS SHALL NOT BE LIABLE FOR ANY:

• Direct damages
• Indirect damages
• Consequential damages
• Incidental damages
• Special damages
• Punitive damages
• Exemplary damages
• Lost profits
• Lost revenue
• Lost business opportunities
• Business interruption damages
• Loss of use
• Loss of data
• Property damage
• Personal injury
• Bodily injury
• Death
• Government fines
• Civil penalties
• Violations
• Citations
• Inspection failures
• Enforcement actions
• Attorney fees
• Litigation expenses
• Regulatory actions

WHETHER ARISING FROM CONTRACT, TORT, NEGLIGENCE, STRICT LIABILITY, PRODUCT LIABILITY, WARRANTY, STATUTE, EQUITY, OR ANY OTHER LEGAL THEORY.

MAXIMUM LIABILITY CAP

IN ALL CIRCUMSTANCES, THE MAXIMUM AGGREGATE LIABILITY OF OUR COMPANY SHALL NOT EXCEED THE ACTUAL PURCHASE PRICE PAID FOR THE SPECIFIC PRODUCT THAT GAVE RISE TO THE CLAIM.

INDEMNIFICATION

The customer agrees to defend, indemnify, and hold harmless our company, its owners, family members, officers, employees, contractors, affiliates, successors, and assigns from and against any and all claims, demands, damages, losses, liabilities, penalties, fines, judgments, settlements, costs, expenses, and attorney fees arising from:

• Product use
• Product misuse
• Product installation
• Product modification
• Regulatory non-compliance
• Inspection failures
• Customer-provided content
• Customer instructions
• Property conditions
• Building conditions
• Third-party claims

THIRD-PARTY LINKS AND EXTERNAL RESOURCES

Any hyperlinks or references to government agencies, websites, laws, regulations, standards, organizations, publications, or third-party resources are provided solely as a convenience.

We do not control, endorse, verify, guarantee, maintain, or assume responsibility for third-party content and shall not be liable for any reliance placed upon such content.

GOVERNING LAW AND VENUE

This Legal Disclaimer, Limitation of Liability, and Terms of Use shall be governed by and construed under the laws of the State of New York, without regard to conflict-of-law principles.

Any dispute, claim, or legal proceeding shall be brought exclusively in the state or federal courts located within the State of New York.

ACCEPTANCE OF TERMS

By accessing our website, downloading materials, receiving information, purchasing products, requesting services, viewing content, or using any product, document, publication, flyer, guide, brochure, checklist, sign, or informational material provided by our company, the user acknowledges that they have read, understood, and agreed to be bound by this Legal Disclaimer, Limitation of Liability, and Terms of Use.

View AllClose